TECH i-1 CWU heating circuit controller weather-compensated – mixing valve + hot water pump
TECH i-1 CWU heating circuit controller weather-compensated – mixing valve + hot water pump is in stock and will be shipped as soon as it is available again
Delivery and shipping
Delivery and shipping
Processing time is typically 1 business day. Delivery for parcels is 1-3 business days. For freight forwarding, delivery time is 3-5 business days. Delivery times outside Germany vary.
Description
Description
TECH i-1 CWU weather-compensated heating circuit controller – mixing valve + DHW pump
Product description
The weather-compensated heating circuit controller TECH i-1 CWU (EU-i-1 DHW) It controls a 3/4-way mixing valve including a valve pump and an additional hot water pump. Via an outdoor sensor (weather compensation), weekly program, and room thermostat connection, it maintains a stable flow temperature and enables... Backflow protection On the boiler. Ideal for modernization and new construction – for private homeowners as well as for installers.
Highlights
- Stepless valve control + pump control (heating circuit pump/valve pump, DHW pump)
- Hot water control: Setpoint 40–70 °C, Hysteresis adjustable
- Valve operating modes: radiator circuit, underfloor heating, return protection
- Expandable up to 3 mixing valves (via add-on modules)
- Optional remote access possible via add-on module
Areas of application
- Suitable for
- Heating systems with 3-/4-way mixing valve (radiators or underfloor heating)
- Boiler/buffer systems where backflow protection is required
- Hot water storage tank with separate charging pump (circulation/charging pump depending on the system)
- Not suitable for
- Systems without a mixing valve
- Consumers at the exits with > 0.5 A Load (per output)
- Pure 24V systems without a 230V power supply
Technical data
- Supply: 230 V ±10%/50 Hz – Standard mains connection in the heating sector
- Own consumption: 3 W – very low power consumption in continuous operation
- Maximum output load: pump 0.5 A, valve 0.5 A – maximum switching/control load per output
- Potential-free contact: 230 V AC 0.5 A (AC1)/24 V DC 0.5 A (DC1) – e.g. for enabling/requesting external components
- Temperature ranges:
- Device: 5–50 °C (Vicinity)
- Sensor: -30…99 °C (Measuring range)
- Measurement accuracy: ±1 °C
- Dimensions: 110 × 163 × 57 mm – compact wall mounting possible
- Security: 1.6 A – Device protection via fuse
Scope of delivery
- Heating circuit controller with LCD display (wall-mounted housing)
- Temperature sensors: Boiler/flow, valve/return, outside temperature, hot water
- User manual
Conclusion
The TECH i-1 CWU is a compact, practical solution for weather-compensated control a mixing circuit plus hot waterWith its weekly program, sensors and backflow protection function, it is suitable for both private homes and professional installations.
payment & Security